Rockwell Automation 1760-xxxx Pico GFX-70 Controllers User Manual User Manual

Page 168

Advertising
background image

Publication 1760-UM002B-EN-P - March 2005

4-58 Wiring with Pico GFX-70

Parameters of BT01 function block:
Source range:

>I1 MB15

Destination range:

>I2 64

Number of bytes:

>NO

4

Marker MB01: 1

After a rising edge from 0 to 1 at coil BT01T_ the value 45 is present in the
marker bytes MB65 to MB68.

Example:
Initial is at ion of marker blocks, definition of a range in a different format.

The value of marker byte MB60 is to be transferred to MD80 and MD81.

Parameters of BT01 function block:
Source range:

>I1 MB60

Destination range:

>I2 MD80

Number of bytes:

>

>NO 8

IMPORTANT

Destination range: Constant 64:
Marker MB01 plus Offset: 1 + 64 = 65

→ MB65.

Source range

Value of source
marker range
(decimal)

Destination range

Value of
destination
marker range
(decimal)

MB15

45

MB65

45

MB66

45

MB67

45

MB68

45

IMPORTANT

The transfer is in byte format. MD80 has 4 bytes and
MD81 has 4 bytes, which means that

<NO

has the value 8.

Advertising