Publication 1760-UM002B-EN-P - March 2005

Pico-Link and Point-to-Point Serial Connections 6-21

The time required to detect that the Serial Interface is not working properly
depends on the baud rate selected and the event concerned.

Status of diagnostics contact ID09

Status of the connection

“0”

Serial Interface connection operating
correctly or

no Serial Interface connection selected.

“1”

Serial Interface connection not functioning,
faulty

Baud rate

Time required for detection of faulty Serial Interface connection.

CRC error (data content
incorrect)

No response, no hardware
connection, remote station not
in operation

9600 Baud

250 ms

1.5 s

19200 Baud

120 ms

0.8 s

ATTENTION

If the states of the inputs, outputs or data are
required by a station without fail, the respective
diagnostics contact should be evaluated and the
information applied in accordance with its respective
application.

If the respective diagnostics contacts are not
evaluated, it may cause faults in your application.