Rockwell Automation 1760-xxxx Pico GFX-70 Controllers User Manual User Manual

Page 235

Advertising
background image

Publication 1760-UM002B-EN-P - March 2005

Wiring with Pico GFX-70 4-125

Inputs

The function block input

>I1

can be assigned the following operands:

• Constants
• Markers MD, MW, MB
• Analog inputs IA01 to IA04

IA01: terminal I7

IA02: terminal I8

IA03: terminal I11

IA04: terminal I12

• Analog output QA01
• Actual value

QV> of another function block

BCD code

Decimal value

0001

1

0010

2

0011

3

0100

4

0101

5

0110

6

0111

7

1000

8

1001

9

1010 to 1111

Not permissible

10000

10

10001

11

IMPORTANT

The BCD code only allows the number range 0

hex

to 9

hex

.

The number range A

hex

to F

hex

cannot be represented. The

NC function block converts the impermissible range to 9.