A.10, Gfx i/o modules input specifications, A-10 – Rockwell Automation 1760-xxxx Pico GFX-70 Controllers User Manual User Manual

Page 382

Advertising
background image

Publication 1760-UM002B-EN-P - March 2005

A-10 Specifications

Table A.10 GFX I/O Modules Input Specifications

Specification

1760-IB12XOW4IF, 1760-IB12XOW4IOF
1760-IB12XOB4IF, 1760-IB12XOB4IOF

1760-IA12XOW4I

Number of digital inputs

12

(1)

12

Inputs usable as analog inputs (I7, I8, I11, I12)

4

(1)

0

Inputs usable as high-speed inputs (I1, I2, I3, I4) 4

0

Rated voltage

24V dc

120/240V ac

Off-state voltage

I1 to I6 and I9 to I10: < 5V dc
I7, I8, I11, I12: < 8V dc

0 to 40V ac

On-state voltage

I1 to I6 and I9 to I10: > 15V dc
I7, I8, I11, I12: > 8V dc

79 to 264V ac

On-state current

I1 to I6, I9 to I10 at 24V dc: 3.3 mA
I7, I8, I11, I12 at 24V dc: 2.2 mA

115V ac: 0.2 mA
230V ac: 0.5 mA

Signal delay

Debounce On: 20 ms
Debounce Off, typical:
I1 to I4s: 0.025 ms
I5, I6, I9, I10: 0.25 ms
I7, I8, I11, I12: 0.15 ms

0 to 1: 10 ms

1 to 0: 100 ms

Electrical Isolation

To supply voltage: No
Between each other: No
To the outputs: Yes
To PC interface, memory module, the
Pico-Link network, expansion I/O: Yes

To supply voltage: No
Between each other: No
To the outputs: Yes
To PC interface, memory module, the
Pico-Link network, expansion I/O: Yes

Cable Length (unshielded)

100 m (328 ft)

60 m (197 ft)

Number of analog inputs (I7, I8, I11, I12)

4

0

Input type

DC voltage

Signal range

0 to 10V dc

Resolution analog

0.01V

Resolution digital

10-bit (0 to 1023 counts)

Input impedance

11.2K

Accuracy

Two GFX devices, from actual value: ±3%
Within a unit, from actual value, (I7, I8, I11,
I12): ±2%

Input current

< 1 mA

Conversion time, analog to digital

Debounce On: 20 ms
Debounce OFF: each cycle time

Electrical Isolation

To supply voltage: No
To the digital inputs: No
To the outputs: Yes
To the Pico-Link network: Yes

–s

Cable Length (unshielded)

30 m (98 ft)

Advertising