Specifications A-11

Number of high-speed inputs (I1, I2, I3, I4)

4

0

High-speed up and down counters

Frequency: < 3 kHz
Pulse shape: square wave

Frequency counters

Frequency: < 3 kHz
Pulse shape: square wave

Incremental counter encoder

Frequency: < 3 kHz
Pulse shape: square wave
Counter inputs I1 and I2, I3 and I4: 2
Signal offset: 90°

(1) Four of the digital dc inputs can alternately be used as 0 to 10V dc analog inputs. These inputs can be used as either digital or analog, not both. For example, you could use

4 analog inputs plus 8 digital inputs.

Table A.10 GFX I/O Modules Input Specifications

Specification

1760-IB12XOW4IF, 1760-IB12XOW4IOF
1760-IB12XOB4IF, 1760-IB12XOB4IOF

1760-IA12XOW4I

Table A.11 GFX I/O Modules Relay Output Specifications

Specification

1760-IA12XOW4I, 1760-IB12XOW4IF
1760-IB12XOW4IOF, 1760-OW2

Number of relay outputs

4 (2 for the 1760-OW2)

Type of outputs

Relays

In groups of

1

Connection of outputs in parallel to increase the output

Not permissible

Protection for an output relay

Miniature circuit-breaker B16: 16A
or fuse (slow-blow): 8A

Potential isolation to mains power supply, input, PC interface, memory module, Pico-Link
network, expansion I/O

Safe isolation: 300V ac
Basic insulation: 600V ac

Mechanical life span

10 x 10

6

switch operations

Contacts relays

Conventional thermal current, (UL)

8A, (10A)

Recommended for load at 12V ac/dc

> 500 mA

Protected against short-circuit cos

ϕ = 1, 16A characteristic B (B16) at

600A

Protected against short-circuit cos

ϕ = 0.5 to 0.7, 16A characteristic B (B16) at

900A

Rated impulse withstand voltage U

imp

contact coil

6 kV

Rated insulation voltage U

i

Rated operational voltage U

e

250V ac

Safe isolation to EN 50178 between coil and contact

300V ac

Safe isolation to EN 50178 between two contacts

300V ac

Making capacity, IEC 60947

AC-15 250V ac, 3A (600 Ops/h)

300,000 switch operations

DC-13 L/R

≤ 150 ms 24V dc, 1A (500 Ops/h)

200,000 switch operations

Breaking capacity, IEC 60947

Advertising