Publication 1760-UM002B-EN-P - March 2005

4-76 Wiring with Pico GFX-70

Wiring of a Frequency Counter

You integrate a frequency counter into your circuit in the form of a contact
and coil. The counter relay has different coils and contacts.

Figure 4.31 Pico GFX-70 circuit diagram with frequency counter

Parameter display and parameter set for frequency counter:

In the parameter display of a counter relay you change set point values and/or
the preset value and the enable of the parameter display.

Value Range

The function block operates in the integer range from 0 to 5000
1 kHz 1 = 1000

Behavior when value range is exceeded

The value range cannot be exceeded as the maximum measured value is less
than the value range.

Inputs

The function block inputs

>SH

and

>SL

can have the following operands:

IMPORTANT

To prevent unpredictable switching states, use each coil of a
relay once only in the circuit diagram. Use a counter input
for the CF, CH, CI counters only once.

I 05---------------------------[ CF01EN

CF01OF-------------------------[ Q 01

CF01FB-------------------------[ Q 02

CF01ZE-------------------------[ Q 03

CF01 -

>SH

>SL

QV>

CF01

Frequency counter function block number 01

-

Does not appear in the parameter display

>SH

Upper set point

>SL

Lower set point

QV>

Actual value in RUN mode