Monitoring of Short-Circuit
and Overload with
1760-IB12XOB8

Depending on the type of expansion module in use, it is possible to use the
internal inputs I16, R15 and R16 to monitor for short-circuits or overloads on
an output.

• Pico GFX-70:

I16: Group fault signal for outputs Q1 to Q4.

• 1760-IB12XOB8:

R16: Group fault signal for outputs S1 to S4.

R16: Group fault signal for outputs S5 to S8.

Examples

The following examples are for I16 = Q1 to Q4.

Example 1: Selecting an Output with Fault Indication

Figure 8.5 Circuit diagram for fault output via I16

The above circuit diagram functions as follows:

If a transistor output reports a fault, M16 is set by I16. The break contact of
M16 switches off output Q1. M16 can be cleared by resetting the Pico
GFX-70 power supply.

Example 2: Output of Operating State

Figure 8.6 Output of operating state

State

Outputs

I16, R15 or R16

No fault found

“0” = switched off (make contact)

At least one output has a fault

“1” = switched on (make contact)

IMPORTANT

I16 can only be edited with Pico GFX-70 versions which
have transistor outputs.

I 01----M 1

6-------------------[ Q 01

I 16--------------------------S M 16

I 01----M 16-------------------[ Q 01

I 16---------------------------S M 16

M 16---------------------------[ Q 04