Publication 1760-UM002B-EN-P - March 2005

Wiring with Pico GFX-70 4-93

Contacts

A contact has been assigned to the text output function block.
D01Q1 to D32Q1, text function block is active.

Coils

D01EN to D32EN, enable of the text function block

Memory Requirement of the Text Output Function Block

The text output function block function block requires 160 bytes of memory.
This is irrespective of the text size.

Data Function Block

The data function block allows you to selectively save a value. Setpoint values
for the function block can be saved in this manner.

Figure 4.39 Pico GFX-70 circuit diagram with data function block:

Parameter display and parameter set for the data function block:

Inputs

The function block input

>I1

can be assigned the following operands:

• Constants
• Markers MD, MW, MB
• Analog inputs IA01 to IA04

IA01: terminal I7

IA02: terminal I8

GT01Q1---------------------------[ DB16T

DB16Q1---------------------------S D 02EN

DB16

+

>I1

QV>

DB16

Data block function block number 16

+

Appears in the parameter display

>I1

Input value

QV>

Actual value