Rockwell Automation 1760-xxxx Pico GFX-70 Controllers User Manual User Manual

Page 172

Advertising
background image

Publication 1760-UM002B-EN-P - March 2005

4-62 Wiring with Pico GFX-70

Parameters of BT01 function block:
Source range:

>I1 MB15

Destination range:

>I2 64

Number of bytes:

>NO

4

Marker MB01: 1

After a rising edge from 0 to 1 at coil BT01T_ the content of MB15 to MB18
is copied to the marker bytes MB65 to MB68.

Example:
Copying of marker blocks, definition of a marker range in a different format.

The value of marker byte MD60 to MD62 is to be copied to MW40 to MW45.

Parameters of BT01 function block:
Source range:

>I1 MD60

Destination range:

>I2 MW40

Number of bytes:

>NO 12

IMPORTANT

Destination range: Constant 64:
Marker MB01 plus Offset: 1 + 64 = 65

→ MB65.

Source range

Value of source
marker range
(decimal)

Destination range

Value of
destination
marker range
(decimal)

MB15

68

MB65

68

MB16

189

MB66

189

MB17

203

MB67

203

MB18

3

MB68

3

IMPORTANT

The transfer is in byte format. 12 bytes are to be copied.
The range MD60 to MD62 is 12 bytes. This is copied to the
range MW40 to MW45.

Advertising