Publication 1760-UM002B-EN-P - March 2005

4-142 Wiring with Pico GFX-70

Variable Setpoint Values

Behavior of the setpoint value when variable values are used.

• Variable values can be used.
• Variable values must be transferred using operands.
• With the time base “s” the value is accepted as a “value in ms”.
• The last position is rounded up to a zero or five.
• With the time base “M:S” the value is accepted as a “value in s”.
• With the time base “H:M:” the value is accepted as a “value in M

(minutes)”.

Example:

Time base “s”
The operand has the value 9504.
The time value is 9.50s.
The Operand value is 45507.
The time value is 45.510s.

Time base "M:S"
The operand has the value 5999.
The time value is 99 min, 59s. This is the maximum value.

Time base "H:M"
The operand has the value 5999.
The time value is 99 hours, 59 min.

Displaying the Parameter Set in the PARAMETERS Menu

• + Access enabled
• - Access disabled

Contacts

T 01Q1 to T 32Q1

Coils

• T 01EN to T 32EN: trigger coil;
• T 01RE to T 32RE: reset coil;
• T 01ST to T 32ST: stop coil.

IMPORTANT

The delay times are the same as described for the constants.