Installation 2-35

Cable Length and Cross-Sections

For correct operation of the network, the cable lengths, cross-sections and
cable resistances must correspond to the following table.

The surge impedance of the cables used must be 120

.

Calculating the Cable Length with Known Cable Resistance

If the resistance of the cable per unit of length is known (resistance per unit
length R’ in

/m), the entire cable resistance R

L

must not exceed the following

values. R

L

depends on the selected baud rates:

l

max

= maximum cable length in m

R

L

= Total cable resistance in

R’ = Cable resistance per unit length in

/m

Table 2.43

Cable length

Cable Resistance

Cross-section

m

m

/m

mm

2

AWG

up to 40

≤ 140

0.13

26

up to 175

≤ 70

0.25 to 0.34

23, 22

up to 250

≤ 60

0.34 to 0.5

22, 21, 20

up to 400

≤ 40

0.5 to 0.6

20, 19

up to 600

≤ 26

0.75 to 0.8

18

up to 1000

≤ 16

1.5

16

Baud rate

Cable resistance R

L

kBaud

10 to 125

≤ 30

250

≤ 25

500

1000

≤ 12

l

max

= R

L

R’