Inputs

The function block inputs

>I1

and

>I2

can have the following operands:

• Constants
• Markers MD, MW, MB
• Analog inputs IA01 to IA04

IA01: terminal I7

IA02: terminal I8

IA03: terminal I11

IA04: terminal I12

• Analog output QA01
• Actual value

QV> of another function block

Actual Value

QV>

The actual value

QV> can be assigned the following operands:

• Markers MD, MW, MB
• Analog output QA01

Table 4.65 Time Range

Parameter

Time range and setpoint time

Resolution

S 000.000

Seconds, 0.005 to 999.995s for constants and
variable values

5 ms

M:S 00:00

Minutes: Seconds 00:00 to 99:59 only for constants
and variable values

1 s

H:M 00:00

Hours: Minutes, 00:00 to 99:59 only for constants
and variable values

1 min.

IMPORTANT

Minimum time setting:
0.005 s (5 ms).

If a time value is less than the Pico GFX-70 cycle time, the
elapsed time will only be recognized in the next cycle.