Wiring with Pico GFX-70 4-141
Inputs
The function block inputs
>I1
and
>I2
can have the following operands:
• Constants
• Markers MD, MW, MB
• Analog inputs IA01 to IA04
–
IA01: terminal I7
–
IA02: terminal I8
–
IA03: terminal I11
–
IA04: terminal I12
• Analog output QA01
• Actual value
…
QV> of another function block
Actual Value
…
QV>
The actual value
…
QV> can be assigned the following operands:
• Markers MD, MW, MB
• Analog output QA01
Table 4.65 Time Range
Parameter
Time range and setpoint time
Resolution
S 000.000
Seconds, 0.005 to 999.995s for constants and
variable values
5 ms
M:S 00:00
Minutes: Seconds 00:00 to 99:59 only for constants
and variable values
1 s
H:M 00:00
Hours: Minutes, 00:00 to 99:59 only for constants
and variable values
1 min.
IMPORTANT
Minimum time setting:
0.005 s (5 ms).
If a time value is less than the Pico GFX-70 cycle time, the
elapsed time will only be recognized in the next cycle.