Rockwell Automation 1760-xxxx Pico GFX-70 Controllers User Manual User Manual
Page 201

Publication 1760-UM002B-EN-P - March 2005
Wiring with Pico GFX-70 4-91
Figure 4.37 Pico GFX-70 circuit diagram with comparator
Parameter display and parameter set for the comparator function block:
Inputs
The function block inputs
>I1
and
>I2
can have the following operands:
• Constants
• Markers MD, MW, MB
• Analog inputs IA01 to IA04
–
IA01: terminal I7
–
IA02: terminal I8
–
IA03: terminal I11
–
IA04: terminal I12
• Analog output QA01
• Actual value
…
QV> of another function block
Contacts
• CP01LT to CP32LT, (less than)
Contact (make contact) switches to status 1, if the value on
>I1
is less than the
value on
>I2
;
>I1
<
>I2
.
• CP01EQ to CP32EQ, (equal to)
Contact (make contact) switches to status 1, if the value on
>I1
is equal to the
value on
>I2
;
>I1
=
I2
.
• CP01GT to CP32GT, (greater than)
CP32LT-------------------------S Q 01
CP32EQ-------------------------S Q 02
CP32GT------------------------
|
R Q 01
|R Q 02
CP02 +
>I1
>I2
CP02
Function block analog value comparator number 02
+
Appears in the parameter display
>I1
Comparison value 1
>I2
Comparison value 2