Rockwell Automation 1760-xxxx Pico GFX-70 Controllers User Manual User Manual
Page 208

Publication 1760-UM002B-EN-P - March 2005
4-98 Wiring with Pico GFX-70
Value Range for Inputs and Outputs
Example:
Displaying the Parameter Set in the PARAMETERS Menu
• + Access enabled
• - Access disabled
Contacts
DC01LI to DC32LI, value range of the manipulated variable exceeded.
Coils
• DC01EN to DC32EN: Enable PID controller;
• DC01EP to DC32EP:Activate proportional component;
• DC01EI to DC32EI:Activate integral component;
Value range
Resolution/unit
>I1
Setpoint of PID controller
-32768 to +32767
>I2
Actual value of PID controller, -32768 to +32767
>KP
Proportional gain K
p
0 to 65535
in -- /%
>TN
Reset time T
n
0 to 65535
in 100/ms
>TV
Rate time T
v
0 to 65535
in 100/ms
>TC
Scan time
0 to 65535
in 100/ms
>MV
Manual manipulated variable
-4096 to +4095
QV>
Manipulated variable
0 to 4095 (unipolar)
-4096 to +4095 (bipolar)
Value at input
Value processed in
the function block.
>KP
Proportional gain K
p
1500
15
>TN
Reset time T
n
250
25 s
>TV
Rate time T
v
200
20 s
>TC
Scan time
500
50 s
>MV
Manual manipulated variable 500
500