Publication 1760-UM002B-EN-P - March 2005

2-36 Installation

Calculating Cross-Section with Known Cable Lengths

The minimum cross-section is determined for the known maximum extent of
the network.

l = cable length in m

S

min

= minimum cable cross-section in mm

2

ρ

cu

= resistivity of copper, if not otherwise stated 0.018

mm

2

/m

Calculating Length with Known Cable Cross-Section

The maximum cable lengths are calculated for a known conductor
cross-section.

l

max

= cable length in m

S = minimum cable cross-section in mm

2

ρ

cu

= resistivity of copper, if not otherwise stated 0.018

mm

2

/m

Plugging and Unplugging Network Cables

Pico GFX-70 is provided with two RJ45 network sockets.

The socket 1 in the first station is for the bus terminating resistor. For other
stations, socket 1 is used for plugging in the incoming cable. Socket 2 is used
for the outgoing cable or for the bus termination resistor on the last physical
station in the network.

S

min

= l x

ρ

cu

12.4

IMPORTANT

If the result of the calculation does not yield a standard
cross-section, the next larger cross-section is used.

l

max

= S x 12.4

ρ

cu