Displaying the status display of other stations – Rockwell Automation 1760-xxxx Pico GFX-70 Controllers User Manual User Manual

Page 96

Advertising
background image

Publication 1760-UM002B-EN-P - March 2005

3-18 Commissioning

The NET parameters are modified as described for inputting parameters for
the first time.

Station addresses in the STATIONS menu are changed as follows:

1.

Go to the physical location which is to be modified.

2.

Press the OK button.

3.

Select the required station number and confirm your input with the OK
button.

4.

Configure all Pico-Link stations again using the CONFIGURATION
menu.

Further information concerning the Pico-Link network topic can be found in
Pico-Link and Point-to-Point Serial Connections on page 6-1.

Displaying the Status Display of Other Stations

On every device with a display, you can display the states of the inputs and
outputs of each network station.

IMPORTANT

Existing station numbers can only be modified to
free, non-assigned station numbers. If all eight
numbers are assigned, all station numbers which are
to be modified must be set to zero. Thereafter, all
station numbers can be reassigned. (Pico GFX-70 sets all
station numbers to zero which are assigned a physical
location behind the leading zero.)

Advertising