3-18 Commissioning
The NET parameters are modified as described for inputting parameters for
the first time.
Station addresses in the STATIONS menu are changed as follows:
1.
Go to the physical location which is to be modified.
2.
Press the OK button.
3.
Select the required station number and confirm your input with the OK
button.
4.
Configure all Pico-Link stations again using the CONFIGURATION
menu.
Further information concerning the Pico-Link network topic can be found in
Pico-Link and Point-to-Point Serial Connections on page 6-1.
Displaying the Status Display of Other Stations
On every device with a display, you can display the states of the inputs and
outputs of each network station.
IMPORTANT
Existing station numbers can only be modified to
free, non-assigned station numbers. If all eight
numbers are assigned, all station numbers which are
to be modified must be set to zero. Thereafter, all
station numbers can be reassigned. (Pico GFX-70 sets all
station numbers to zero which are assigned a physical
location behind the leading zero.)