Rockwell Automation 1760-xxxx Pico GFX-70 Controllers User Manual User Manual

Page 236

Advertising
background image

Publication 1760-UM002B-EN-P - March 2005

4-126 Wiring with Pico GFX-70

Actual Value

QV>

The actual value

QV> can be assigned the following operands:

• Markers MD, MW, MB
• Analog output QA01

Displaying the Parameter Set in the PARAMETERS Menu

• + Access enabled
• - Access disabled

Coil

NC01EN to NC32EN: enable coil.

Memory Requirement of the Numerical Converter

The numerical converter function block requires 32 bytes of memory plus 4
bytes per constant on the function block input.

Function of the Numerical Converter Function Block

BCD Mode

The BCD value at

>I1

is provided in decimal format at the input. The binary

value is formed from this. The binary value is interpreted as a BCD value.
Values greater than 9 (1001) are set to the value 9. The BCD value is output as
a decimal value at the output QV>.

Example 1:
Input value >I1: +9

dec

Binary value: 1001
Decimal value QV>: + 9

Example 2:
Input value>I1: +14

dec

Binary value: 1110
Decimal value QV>: + 9

IMPORTANT

The numerical converter function block must be enabled so
that it can work. Coil NC..EN is active. If coil NC..EN is
not active, the entire function block is deactivated and reset.
The output value is set to zero.