Connecting dc inputs -23, Connecting dc inputs – Rockwell Automation 1760-xxxx Pico GFX-70 Controllers User Manual User Manual

Page 57

Advertising
background image

Publication 1760-UM002B-EN-P - March 2005

Installation 2-23

A resistor can be connected in series with the circuit shown in order to restrict
the inrush current.

Figure 2.24 Limitation of the inrush current with a resistor

Connecting DC Inputs

Use input terminals I1 to I12 to connect push button actuators, switches or 3
or 4-wire proximity switches. Given the high residual current, do not use
2-wire proximity switches.

Input signal voltage range

• I1 to I6, I9, I10

OFF signal: 0V dc to 5V dc

ON signal: 15V dc to 28.8V dc

• I7, I8, I11, I12

OFF signal: < 8V dc

ON signal: > 8V dc

Input current

• I1 to I6, I9, I10, R1 to R12: 3.3 mA at 24V dc
• I7, I8, I11, I12: 2.2 mA at 24V dc

IMPORTANT

When using a 100 nF capacitor, the drop-out time of the
input increases by 80 (66.6) ms at 50 (60) Hz.

L1

N

R10

R9

R8

R7

R6

R5

R4

R3

R2

R1

E+ E–

R11 R12

N

N

L

100-240V

F1

100 nF/275 V

h

1 k

O

Advertising