A-16 Specifications
Table A.17 Pico-Link Specifications
Specification
1760-LDFC and 1760-LDFCA
Number of stations
8
Bus length/transmission speed
(1)
(1)
Bus lengths above 40 m can only be achieved with cables with reinforced cross-section
and connection adapter.
6m/1000k Baud
25m/500k Baud
40m/250k Baud
125m/125k Baud
300m/50k Baud
700m/20k Baud
1000m/10k Baud
Electrical isolation
To power supply, inputs, outputs, expansion
I/O, PC interface, memory module: Yes
Bus termination (see accessories)
Yes (First and last station)
Plug connector (see accessories)
8 poles
RJ45
Cable cross-sections, with cable lengths and cable resistance/m
Cross-section up to 1000, < 16 m
Ω/m
1.5 mm
2
(16 AWG)
Cross-section up to 600, < 26 m
Ω/m
0.75 mm
2
to 0.8 mm
2
(18 AWG)
Cross-section up to 400, < 40 m
Ω/m
0.5 mm
2
to 0.6 mm
2
(20, 19 AWG)
Cross-section up to 250, < 60 m
Ω/m
0.34 mm
2
to 0.5 mm
2
(22, 21, 20) AWG
Cross-section up to 175, < 70 m
Ω/m
0.25 mm
2
to 0.34 mm
2
(23, 22 AWG)
Cross-section up to 40, < 140 m
Ω/m
0.13 mm
2
(26 AWG)