Publication 1760-UM002B-EN-P - March 2005

Pico-Link and Point-to-Point Serial Connections 6-7

Configuring the Pico-Link

The Pico-Link can be configured so that it can be optimized for your
application.

Station Number

The station number is identified as the Pico-Link ID in the device. The station
number can be set on devices with a display using the buttons on the Pico
GFX-70.

Valid station numbers for operation are 01 to 08.

Station number 00 = factory default setting

With station number 00, double address assignment cannot occur when an
existing device is being exchanged.

Transmission Speed

The Pico GFX-70 device hardware allows you set transmission speeds
between 10 and 1000 kBaud in specific stages. The length of all cables is
determines the maximum permissible data transfer rate (see General on page
A-1).

The data transfer rate is set under the BAUDRATE: menu item.

Possible baud rates are: 10, 20, 50, 125, 250, 500 and 1000 KB

125 KB = factory default setting

IMPORTANT

All the Pico-Link settings are best carried out on station 1.
The entire network can be configured via station 1. The
configuration should only be carried out locally when a
device is replaced.