Rockwell Automation 1760-xxxx Pico GFX-70 Controllers User Manual User Manual
Page 226
![background image](/manuals/579694/226/background.png)
Publication 1760-UM002B-EN-P - March 2005
4-116 Wiring with Pico GFX-70
Parameter Display and Parameter Set for the LS Function Block
Inputs
The function block inputs
>I1
,
>X1
,
>X2
,
>Y1
and
>Y2
can have the following
operands:
• Constants
• Markers MD, MW, MB
• Analog inputs IA01 to IA04
–
IA01: terminal I7
–
IA02: terminal I8
–
IA03: terminal I11
–
IA04: terminal I12
• Analog output QA01
• Actual value
…
QV> of another function block
Output
The function block output QV> can be assigned the following operands:
• Markers MD, MW, MB
• Analog output QA01
LS27 +
>I1
>X1
>Y1
>X2
>Y2
QV>
LS27
LS value scaling function block number 27
+
Appears in the parameter display
>I1
Input value, actual value source range
>X1
Lower value of source range
>Y1
Lower value of target range
>X2
Upper value of source range
>Y2
Upper value of target range
QV>
Output value, scaled