Publication 1760-UM002B-EN-P - March 2005

Installation 2-21

Figure 2.21 1760-IA12XOW6I Expansion unit

Connect the inputs, for example, to push button actuators, switches or
relay/contactor contacts.

Input signal voltage range

• OFF signal: 0V ac to 40V ac
• ON signal: 79V ac to 264V ac

Input current

• R1 to R12

0.5 mA/0.25 mA at 230V ac/115V ac

Cable Lengths

Severe interference can cause a “1” signal on the inputs without a proper signal
being applied. Observe therefore the following maximum cable lengths:

• R1 to R12: 40m without additional circuit

The following applies to expansion units:

With longer cables, connect a diode (e.g. 1N4007) for 1A, minimum 1 000V
reverse voltage, in series to the input. Ensure that the diode is pointing towards
the input as shown in the circuit diagram, otherwise the module will not detect
the 1 state.

L1

N

R10

R9

R8

R7

R6

R5

R4

R3

R2

R1

E+ E–

R11 R12

N

N

L

100-240 V

F1