Publication 1760-UM002B-EN-P - March 2005
Pico-Link and Point-to-Point Serial Connections 6-13
Evaluation occurs at the following intervals:
If the absence of a “sign of life” is detected, the respective diagnostics contact
is set to 1.
Baud rate
Stations must send a “sign of
life” every ...
Stations recognize the absence
of a “sign of life” signal after
[KB]
[ms]
[ms]
1000
60 180
500
60 180
250
120 360
125
240 720
50
600 1800
20
1500 4500
10
3000 9000
Diagnostics contact
Station number
ID 01
1
ID 02
2
ID 03
3
ID 04
4
ID 05
5
ID 06
6
ID 07
7
ID 08
8