Rockwell Automation 1760-xxxx Pico GFX-70 Controllers User Manual User Manual
Page 243

Publication 1760-UM002B-EN-P - March 2005
Wiring with Pico GFX-70 4-133
Figure 4.58 Pico GFX-70 circuit diagram with pulse width modulation
Parameter Display and Parameter Set for Pulse Width Modulation
The parameter display for a timing relay is used to modify the period duration,
the minimum on time and the enabling of the parameter display.
Value and Time Ranges
Inputs
The function block inputs
>SV
,
>PD
and
>ME
can be assigned the following
operands:
• Constants
• Markers MD, MW, MB
• Analog inputs IA01 to IA04
–
IA01: terminal I7
–
IA02: terminal I8
–
IA03: terminal I11
–
IA04: terminal I12
M 95---------------------------[ PW01EN
PW01E1-------------------------[ M 96
PW02 +
>SV
>PD
>ME
PW02
Pulse width modulation function block number 02
+
Appears in the parameter display
>SV
Manipulated variable input
>PD
Period duration in ms
>ME
Minimum on duration, minimum off duration in ms
Parameter
Value and time range
Resolution
SV
0 to 4095
1 digit
PD
0 to 65535
m
ME
0 to 65535
ms
IMPORTANT
The minimum time setting for the period duration is: 0.005
s (5 ms)