Adjusting Voltage and Current Regulation Parameters

1.

2.

3.

4.

5. Set P105 to the desired negative I

d

current limit between -40 and

0%.

6. Refer to P93 for the final voltage loop I

d

command between -60

and 60%.

If you want the I

d

mode select to be:

Then set P103 to:

Zero (factory default)

0

A constant value

1

From an auxiliary Id

2

The sum of a constant value and an auxiliary Id

3

If P103 is set to:

Then:

1 or 3

Set P102 to the desired I

d

current command between -

40% and 60%. A value of zero is default and should be
used for most applications.

If P103 is set to:

Then:

2 or 3

Set P101 to the desired auxiliary I

d

current command

between -40 and 60%.

If P103 is set to:

Then:

0

I

d

parameter (P93) will be zero.