Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 147

Advertising
background image

Publication 2364F-5.01– October 2003

Programming Parameters

D-3

6

Unit Selection
[Unit Selection]

This parameter selects the units (display or drive)
to be shown on the display.

Selection 0 (Display Units) is recommended for
setup and drive operation.

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0

Minimum Value

0

Maximum Value

1

Related Parameters

None

Value Description

0

Display Units

1

Drive Units

7

P7 is for internal use only.

8

Remote/Local Selector
[Rem/Loc Selector]

This parameter determines if a HIM, GPT, or
SCANport device can Enable or disable the RGU.

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

1

Minimum Value

0

Maximum Value

1

Related Parameters

None

Value Description

0

Local Only

The RGU will modulate when the M1 contactor closes. A HIM, GPT, or SCANport device
cannot start or Enable the RGU, but the Stop is always active.

1

Remote+Local

The HIM, GPT, or SCANport device can be used to Enable or Disable the RGU.