Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 205

Advertising
background image

Publication 2364F-5.01– October 2003

Programming Parameters

D-61

326

Trend 3 Select
[Trend Select]

This parameter commands the RGU to enable,
disable, or force trigger Trend 3.

After the RGU processes the command, the value
resets to 3 (No Command).

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

3 (No Command)

Minimum Value

0

Maximum Value

3

Related Parameters

P317 to P328 (See also P298)

Value Description

0

DisableCommands the RGU to disable Trend 3.

1

EnableCommands the RGU to enable Trend 3.

2

Force TrigCommands the RGU to force trigger Trend 3. The trending value (prescribed by P317) will be sent to Trend 3 Output Indirect (P328).

3

No CommandIndicates that no command is issued at this time.

327

Trend 3 Status
[Trend Status]

This parameter displays the status of Trend 3.

Parameter Type

Sink (Read Only)

Display Units

None

Drive Units

Display Units * 1

Factory Default

1 (Unprogrammed)

Minimum Value

0

Maximum Value

4

Related Parameters

P317 to P328 (See also P298)

Value Description

0

UnprogrammedTrend 3 is not programmed.

1

StoppedThe trending operation is stopped (trend X and trend Y values are not being evaluated).

2

RunningThe trending operation is running (trend X and trend Y values are being evaluated).

3

TriggeredThe trending operation between trend X and trend Y is true. The trending value (determined by P317) will be output through P328.

4

Forced TrigTrend 3 is triggered due to a ‘Force Trig’ command from the Trend 3 Select (P326 = 0). The trending value is output.

328

Trend 3 Output Indirect
[Trend Out Ind]

This parameter prescribes the destination of the
trend parameter value (listed in P317). The
trending operation (X [operator] Y) must be
evaluated as true for P328 to output the value
from the trend source in P317.

Parameter Type

Sink (Read/Write)

Display Units

Parameter Number

Drive Units

Display Units * 1

Factory Default

0 (no selection)

Minimum Value

0

Maximum Value

Maximum Defined Parameter Number

Related Parameters

P317 to P327 (See also P298)

329

Trend 4 Input Indirect
[Trend In Ind]

This parameter designates the parameter to be
output when Trend 4 is triggered.

The source parameter defined here is passed to
the output (P328) when the trending operation is
evaluated as true.

Parameter Type

Sink (Read/Write)

Display Units

Parameter Number

Drive Units

Display Units * 1

Factory Default

0 (no selection)

Minimum Value

0

Maximum Value

Maximum Defined Parameter Number

Related Parameters

P330 to 340 (See also P298)

330

Trend 4 Operand Indirect X
[Trend X Ind]

This parameter designates a source parameter to
be analyzed in the Trend 4 evaluation. The
source value is masked with the trend Y value
(P332 or P333).

Parameter Type

Sink (Read/Write)

Display Units

Parameter Number

Drive Units

Display Units * 1

Factory Default

0 (disabled, P331 enabled)

Minimum Value

0

Maximum Value

Maximum Defined Parameter Number

Related Parameters

P329 to 340 (See also P298)

P331 (Trend 4 X Value) is used as the trend X
operand when this parameter is zero (default).