Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 199

Advertising
background image

Publication 2364F-5.01– October 2003

Programming Parameters

D-55

298

Trend 1 Operator
[Trend Operator]

This parameter selects the operation to be
performed between trend X (P294 or P295) and
trend Y (P296 or P297). If trending is enabled
(P302), a true result of the operation will cause
the Trend 1 Input parameter value (from P293) to
be passed to the prescribed output (P293).

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0 (GT)

Minimum Value

0

Maximum Value

7

Related Parameters

P293 to P304

299

Trend 1 Sample Rate
[Trend Samp Rate]

This parameter determines the rate of sampling
for the Trend 1 Indirects (P294, P296).

The value of this parameter can be changed in
increments of 0.002 sec.

Parameter Type

Sink (Read/Write)

Display Units

sec

Drive Units

Display Units * 2000

Factory Default

0.000

Minimum Value

0.000

Maximum Value

30.000

Related Parameters

P293 to P304 (See P298)

300

Trend 1 Post Samples
[Trend Post Samp]

This parameter defines the number of samples
(out of 500) to be allocated for post-trigger
sampling.

Pre-samples + Post samples = 500 (0 to 499)

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

10

Minimum Value

0

Maximum Value

499

Related Parameters

P293 to P304 (See P298)

Value Description

Value Description

0

GTSelects the operation [Trend X must be greater than Trend Y].

4

ANDSelects the operation [Trend X AND Trend Y].

1

LTSelects the operation [Trend X must be less than Trend Y].

5

NANDSelects the operation [Trend X NAND Trend Y].

2

EQSelects the operation [Trend X must be equal to Trend Y].

6

ORSelects the operation [Trend X OR Trend Y].

3

NESelects the operation [Trend X must not be equal to Trend Y].

7

NORSelects the operation [Trend X NOR Trend Y].

Trend Sampling

Trend Configure

Trend Status

Pttt

Trend

Parameter

Pxxx

Source

Parameter X

Pyyy

Source

Parameter Y

P295

Trend 1
X Value

P294

Trend 1

Operand

Indirect X

P297

Trend 1
Y Value

P296

Trend 1

Operand

Indirect Y

P298

Trend 1

Operator

X [Operator] Y

P293

Trend 1

Input

Indirect

P304

Trend 1

Output

Indirect

Pmmm

Trend

Output

Parameter

P299

Trend 1
Sample

Rate

P300

Trend 1

Post

Samples

P301

Trend 1

Mode

P302

Trend 1

Select

P303

Trend 1

Status