Publication 2364F-5.01– October 2003

5-6

Your Current Code M RGU (Series B)

Table 5.1 Current Code M RGU Symbol to Component Cross Reference

AC 3-Phase Input Voltage

Symbol

Description

Option

"

380V AC

460V AC

575V AC

AM1

Ammeter monitoring L1

800A AC

CB1

Circuit breaker

800A, HND

CH1- 3

Input line reactors

137uH

137uH

191uH

CR2

Fault relay

2 NO/ 2 NC

CT1

Current transducer

800:5

CT1, 3 (EA1)

Current transducers (on EA1)

3000:1, 0-1000A range

EA1

RGU Power structure

EA2

Bus indicator PCB

EA3

Line RC suppressor PCB

EA4

DC bus suppressor assembly

EA10

Control power filter

For 2kHz carrier frequency

F1 (gate drv)

Power supply fuse, gate driver PCB

1A, KTK-R

F1 - 2 (EA2)

Bus indicator PCB fuses (on EA2)

1A, 1000V, KVR, 1-3/32" diameter, 3" length, 500AIC

F1 - 3

Incoming 3-phase, line fuses

1000A, 170M

F2 - 4 (EA1)

Precharge fuses (on EA1)

25A, KLDR

25A, KLDR

30A, KLDR

F4, F6

Primary fuse for a 5 kVA control transformer

25A, KLDR

20A, KLDR

17.5A, KLDR

F7

RGU control power fuse

12A, KLDR

F8

Control bus fuse for a 5 kVA control
transformer

25A, KLDR

F14 - 16

RC suppressor fuses

25A, KTK

F17 - 19 (EA1) AC line sensor fuses (on EA1)

1A, KLDR

M1

Main contactor

600A

M2

Precharge contactor

24A

MTR1 - 2

Door-mounted fan

12", 1200CFM

PL1

DC-Bus-Energized pilot light

24V AC/DC, red, 800MR

PL2

Unit-Not-Faulted pilot light

115V AC, amber, 800MR

PT1

Control power transformer

A 5kVA control transformer is standard. This transformer has multiple taps to
accommodate 380, 460, and 575V AC primary voltages.

R10 - 12,

R10 - 12A

Precharge Resistors

6 ohm, 345 W

S11

Fault reset pushbutton

1 NO, 800MR

S12

Start switch

1 NO/ 1 NC, 800MR

SP1 - 3

Line-to-line MOVs

460 J, 320V AC

460 J, 320V AC

550 J, 385V AC

SP4

Neutral-to-ground MOV

760 J, 680V AC

760 J, 680V AC

760 J, 680V AC

TB1

Terminal Block

600V AC/DC, 22-14AWG, 10 terminals

TB2

Terminal Block

600V AC/DC, 22-14AWG, 2 terminals

TR1

Timer Relay

2 NO/ 2 NC (instantaneous), 1NO / 1 NC (on delay)

VM1

DC bus voltmeter

1000V DC

VM2

Ground fault detection

0-440V AC (meter), NO/NC contacts (relay)

" These components are provided with RGU standard options. Not all RGUs will have these components.