Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 70

Advertising
background image

Publication 2364F-5.01– October 2003

6-6

Your Current Code N RGU (Series B)

Table 6.1 Current Code N RGU Symbol to Component Cross Reference

AC 3-Phase Input Voltage

Symbol

Description

Option

"

380V AC

460V AC

575V AC

AM1

Ammeter monitoring L1

1000A AC

CB1

Circuit breaker

1200A, HND

CH1- 3

Input line reactors

102uH

102uH

144uH

CR2

Fault relay

2 NO/ 2 NC

CR3

Pilot relay

2 NO/ 2 NC

CT1

Current transducer

800:5

CT1, 3 (EA1)

Current transducers (on EA1)

3000:1, 0-1000A range

EA1

Power structure

EA2

Bus indicator PCB

EA3

Line RC suppressor PCB

EA4

DC bus suppressor assembly

EA10

Control power filter

For 2kHz carrier frequency

F1 (gate drv)

Power supply fuse, gate driver PCB

1A, KTK-R

F1 - 2 (EA2)

Bus indicator PCB fuses (on EA2)

1A, 1000V, KVR, 1-3/32" diameter, 3" length, 500AIC

F1 - 3 (EA1)

DC bus fuses (on EA1)

350A, 700V

F1 - 3

Incoming 3-phase, line fuses

1250A, 170M

F2 - 4 (EA1)

Precharge fuses (on EA1)

25A, KLDR

25A, KLDR

30A, KLDR

F4, F6

Primary fuse for a 5 kVA control

transformer

25A, KLDR

20A, KLDR

17.5A, KLDR

Primary fuse for a 10 kVA control

transformer

35A, FRS

30A, KLDR

25A, KLDR

F5

Fan power fuse

10A, KLDR

F7

RGU control power fuse

15A, KLDR

F8

Control bus fuse for a 5 kVA control
transformer

50A, FRN

F14 - 16

RC suppressor fuses

25A, KTK

F17 - 19 (EA1) AC line sensor fuses (on EA1)

1A, KLDR

M2

Precharge contactor

24A

MCP2

Motor circuit protector

30A, HMCP

MTR1 - 3

Door-mounted fan

11", 1100 CFM

MTR4 - 6

Door-mounted fan

7", 340 CFM

PL1

DC-Bus-Energized pilot light

24V AC/DC, red, 800MR

PL2

Unit-Not-Faulted pilot light

115V AC, amber, 800MR

PT1

Control power transformer

A 5kVA control transformer is standard, and a 5kVA control transormer is
available as an option. This transformer has multiple taps to accomodate for
380, 460, and 575V AC primary voltages.

R10 - 12,

R10 - 12A

Precharge Resistors

6 ohm, 345W

S11

Fault reset pushbutton

1 NO, 800MR

S12

Start switch

1 NO/ 1 NC, 800MR

SP1 - 3

Line-to-line MOVs

460 J, 320V AC

460 J, 320V AC

550 J, 385V AC

SP4

Neutral-to-ground MOV

760 J, 680V AC

760 J, 680V AC

760 J, 680V AC

TB1

Terminal Block

600V AC/DC, 22-14AWG, 10 terminals

TB2

Terminal Block

600V AC/DC, 22-14AWG, 2 terminals

TR1

Timer Relay

2 NO/ 2 NC (instantaneous), 1NO / 1 NC (on delay)

VM1

DC bus voltmeter

1000V DC

VM2

Ground fault detection

0-440V AC (meter), NO/NC contacts (relay)

" These components are provided with RGU standard options. Not all RGUs will have these components.