Publication 2364F-5.01– October 2003

D-44

Programming Parameters

217

Simulator Per Unit Capacitance
[Sim Charge Rate]

This parameter defines the capacitance charge
rate to be applied to the bus simulator.

Parameter Type

Sink (Read/Write)

Display Units

msec

Drive Units

Display Units * 1

Factory Default

32

Minimum Value

20

Maximum Value

2000

Related Parameters

P215, P216, P218

218

Simulated Bus Feedback
[Sim Bus Fdbk]

This parameter indicates the simulated bus
feedback determined by P96 (Iq Reference),
P215, P216, and P217.

This value can be used as the source for P141
(Bus Feedback) when P219 = 1 (not default).

Parameter Type

Source (Read Only)

Display Units

Volt

Drive Units

Display Units * 4096/P16

Factory Default

0.00

Minimum Value

0.00

Maximum Value

1.15 x P16

Related Parameters

P215, P216, P217, P219

219

Feedback Select
[Feedback Select]

This parameter selects the feedback source used
for P141 (Bus Feedback). See P140.

Value Description
0

Bus Volt In

Selects the bus feedback

1

Bus Simulate Selects a simulated feedback

Parameter Type

Source (Read Only)

Display Units

Volt

Drive Units

Display Units * 4096/P16

Factory Default

0

Minimum Value

0

Maximum Value

1

Related Parameters

P215, P216, P217, P219

220-223

P220-P223 are for internal use only.

224

SCANport Port Enable Mask
[Port Enable Mask]

This parameter activates SCANport ports.

SCANport 1 = J10 on main control board
SCANport 2 = J9 on main control board
SCANport 6 = J8 on main control board

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0111 1111

Minimum Value

0000 0000

Maximum Value

0111 1111

Related Parameters

P8, P225, P226, P227

Bit

Description

Bit

Description

0

RGU I/OEnables the RGU I/O port

4

SCANport P:4Enables the port for SCANport 4

1

SCANport P:1Enables the port for SCANport 1

5

SCANport P:5Enables the port for SCANport 5

2

SCANport P:2Enables the port for SCANport 2

6

SCANport P:6Enables the port for SCANport 6

3

SCANport P:3Enables the port for SCANport 3

7

Not Used

225

SCANport Enable Mask
[Enable Mask]

This parameter allows a connected SCANport
device to enable the RGU. The selected ports
must be activated (P224).

Parameter Type

Sink (Read/Write)

Display Units

Bits

Drive Units

Display Units * 1

Factory Default

0111 1111

Minimum Value

0000 0000

Maximum Value

0111 1111

Related Parameters

P8, P224, P226, P227

Bit

Description

Bit

Description

0

RGU I/OEnables the RGU I/O

4

SCANport P:4Enables SCANport 4

1

SCANport P:1Enables SCANport 1

5

SCANport P:5Enables SCANport 5

2

SCANport P:2Enables SCANport 2

6

SCANport P:6Enables SCANport 6

3

SCANport P:3Enables SCANport 3

7

Not Used