Overview

1-9

Diode Bridge Operation (RGU Not Enabled)

When the RGU is not enabled, the IGBTs are not modulating. In this
mode, current flows only through the free-wheeling diodes. These
diodes permit current flow in one direction, from anode to cathode.
When an AC voltage is applied to a diode, the output of that diode is a
pulsating DC voltage. This mode is identical to a 3-phase diode
bridge with line reactors.

Operating as a 3-phase diode bridge, the RGU provides an average
DC bus voltage that is approximately 1.35 times the rms line-to-line
voltage. At full load, this average DC bus voltage will decrease to
about 1.24 times the rms line-to-line voltage, due to the line reactors.
Refer to Figure 1.5 for an illustration of the 3-phase AC input voltage
and current waveforms when the RGU is not enabled.

Figure 1.5
3-Phase AC Line Voltage To Neutral and AC Line Current of a Diode Bridge

(RGU Not Enabled)