Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 148

Advertising
background image

Publication 2364F-5.01– October 2003

D-4

Programming Parameters

9

RGU State of Operation
[RGU State]

This parameter indicates the RGU’s state of
operation during the power-up sequence and
during normal operation.

Parameter Type

Source (Read Only)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0

Minimum Value

0

Maximum Value

9

Related Parameters

None

Value Description

0

HW Init

Indicates that the RGU hardware is initiating (startup or reset)

1

No Bus Voltage

Indicates that the DC bus is not yet powered

2

Precharging

Indicates that the RGU is precharging the capacitors

3

Closing M1

Indicates that precharging is complete and the main contactor M1 is closing

4

Flt, M1 Closed

Indicates that the RGU is faulted, M1 is closed

5

Flt, M1 Open

Indicates that the RGU is faulted, M1 is opened

6

HW Failure

Indicates that hardware failure has occured in the RGU

7

Crtl Ready

Indicates that the RGU control is ready for operation

8

Starting Ctrl

Indicates that the RGU control is starting operation

9

Ctrl Running

Indicates that the RGU control is processing

10

Nominal AC Line Voltage
[Nom Line Voltage]

This parameter stores the nominal input line
voltage of the RGU.

Parameter Type

Source (Read/Write)

Display Units

Vrms

Drive Units

Display Units * 1

Factory Default

See below

Minimum Value

See below

Maximum Value

See below

Related Parameters

P4, P14, P26, P27

RGUs with a 380V AC Input

RGUs with a 460V AC Input

RGUs with a 575V AC Input

Factory Default

380

Factory Default

460

Factory Default

575

Minimum Value

198

Minimum Value

207

Minimum Value

258

Maximum Value

418

Maximum Value

506

Maximum Value

633

Hard Fault

Hardware

Initiate

No Bus
Voltage

Precharging

Closing M1

Fault, M1

Closed

Control

Ready

Fault, M1

Open

Starting

Control

Hardware

Failure

Not Hard

Fault

Hardware

Error

Timeout

Timeout or
Bus Not Up

Not

Hard
Fault

Hard
Fault

Control

Running

Hard Fault

Bus

Up

Not Enabled

Advertising