Publication 2364F-5.01– October 2003

Programming Parameters

D-7

27

AC Line High Setting
[Line Hi Setting]

This parameter defines the highest acceptable AC
line voltage. A fault or warning may be indicated
in P180 (Host Fault Status Word 3) if the AC line
voltage exceeds the value of this parameter.

Parameter Type

Sink (Read/Write)

Display Units

Vrms

Drive Units

Display Units * 1

Factory Default

528 (110% of 480V AC)

Minimum Value

0

Maximum Value

800

Related Parameters

P14, P26, P180

RGUs with a 380V AC Input

RGUs with a 460V AC Input

RGUs with a 575V AC Input

Factory Default

436

Factory Default

528

Factory Default

660

28

DC Bus Low Setting
[Bus Low Setting]

This parameter defines the lowest acceptable DC
bus voltage. A fault or warning may be indicated
in P174 (Host Fault Status Word 1) if the DC bus
voltage falls below the value of this parameter.

Parameter Type

Sink (Read/Write)

Display Units

Volt

Drive Units

Display Units * 4096/P16

Factory Default

5/7 * P16

Minimum Value

0

Maximum Value

1.5 * P16

Related Parameters

P16, P29, P141, P174

29

DC Bus High Setting
[Bus Hi Setting]

This parameter defines the highest acceptable DC
bus voltage. A fault or warning may be indicated
in P174 (Host Fault Status Word 1) if the DC bus
voltage exceeds the value of this parameter.

Parameter Type

Sink (Read/Write)

Display Units

Volt

Drive Units

Display Units * 4096/P16

Factory Default

8/7 * P16

Minimum Value

0

Maximum Value

1.5 * P16

Related Parameters

P16, P28, P141, P174

30

DC Bus Voltage Tolerance
[Bus V Tolerance]

This parameter defines the acceptable voltage
tolerance on the DC bus. The DC bus is
considered to be “at voltage” when the value of
P141 (Bus Feedback) is within the range of P126
(Bus Rate Reference) +/- P30.

Parameter Type

Sink (Read/Write)

Display Units

Volt

Drive Units

Display Units * 4096/118

Factory Default

0.005 * P16 (0.5% of P16)

Minimum Value

0

Maximum Value

0.029 * P16 (2.9% of P16)

Related Parameters

P16, P34, P141, P126

When the voltage is within the tolerance, the “Bus
at Volt” bit of P34 (Host Status 2) is set to 1

31

P31 is for internal use only.