Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 150

Advertising
background image

Publication 2364F-5.01– October 2003

D-6

Programming Parameters

16

Nominal DC Bus Voltage
[Nom DC Bus Volts]

This parameter stores the nominal voltage on the
DC bus. The nominal DC bus voltage is
calculated as the nominal AC line voltage
multiplied by the square root of two.

Parameter Type

Source (Read/Write)

Display Units

Volt

Drive Units

Display Units * 1

Factory Default

See below

Minimum Value

See below

Maximum Value

See below

Related Parameters

P4, P28, P29, P30, P141

RGUs with a 380V AC Input

RGUs with a 460V AC Input

RGUs with a 575V AC Input

Factory Default

580

Factory Default

700

Factory Default

848

Minimum Value

200

Minimum Value

200

Minimum Value

200

Maximum Value

800

Maximum Value

800

Maximum Value

1000

17,18

P17 and P18 are for internal use only.

19

Seconds Counter
[Seconds Counter]

This parameter displays a running counter (in
seconds). This can be used to verify that the
system processor is running.

Parameter Type

Source (Read Only)

Display Units

sec

Drive Units

Display Units * 1

Factory Default

0

Minimum Value

0

Maximum Value

65535

20

Master Status
[Master Status]

This parameter displays the status of the master
RGU in a master-slave configuration.

This status is sent to a slave unit through P272
(RGU-to-RGU Transmit Indirect). If this unit is

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

0000 0000 0000 0011

Related Parameters

P5, P272, P274

not the master, the master status is received through
P274 (RGU-to-RGU Receive 1, Indirect 1).

Bit

Description

0

EnabledIndicates that the master unit is enabled.

1

FaultedIndicates that the master unit is faulted.

2-15

Not Used

21-25

P21-P25 are for internal use only.

26

AC Line Low Setting
[Line Low Setting]

This parameter defines the lowest acceptable AC
line voltage. A fault or warning may be indicated
in P180 (Host Fault Status Word 3)if the AC line
voltage drops below the value of this parameter.

Parameter Type

Sink (Read/Write)

Display Units

Vrms

Drive Units

Display Units * 1

Factory Default

See below

Minimum Value

0

Maximum Value

800

Related Parameters

P14, P27, P180

RGUs with a 380V AC Input

RGUs with a 460V AC Input

RGUs with a 575V AC Input

Factory Default

356

Factory Default

432

Factory Default

540