Publication 2364F-5.01– October 2003

D-8

Programming Parameters

32

Host Command Word
[Host Command]

This parameter commands the processor to
perform the function(s) indicated by each fault bit
which is set to 1.

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

0000 1111 1111 1111

Related Parameters

P33, P34, P35

For example, to command the processor to clear
faults, you would enter the command

word, 0000 0000 0000 0001.

Bit

Description

0

Clr Faults

Sends a command to clear faults in the RGU

1

Enable Cmd

Sends a command to Enable RGU control

2

Meter Reset

Sends a command to reset the watt-hour meter

3

Save Command

Sends a command to save parameters

4

Param Recall

Sends a command to reset parameters

5

Default Init

Sends a command to initialize parameters to their defaults

6

Clr Warnings

Sends a command to clear warnings in the RGU

7

Reset Cmd

Sends a command to reset the RGU

8

Clr Flt Que

Sends a command to clear the fault queue

9

Clr Wrn Que

Sends a command to clear the warning queue

10

Disable Cmd

Sends a command to Disable the RGU control

11

Run Startup

Sends a command to reset the RGU and to initiate the startup sequence

12-15 Not Used

33

Host Status Word 1
[Host Status 1]

This parameter indicates a number of conditions
that the RGU is experiencing.

A condition is indicated by the bit being set to 1.
For example, the word, 0000 0011 0100 0000,

Parameter Type

Source (Read Only)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

Related Parameters

P32, P34, P35

indicates that the DC bus is at voltage, the DSP

processor is ready, and control is ready.

Bit

Description

0

Hard Fault

Indicates that a hard fault has occurred.

1

Warning Flt

Indicates that a warning fault has occurred.

2

Clr Faults

Indicates that clear fault command(s) are pending.

3

Clr Warnings

Indicates that clear warning command(s) are pending.

4

BCR Relay

Indicates that the bus control relay is closed.

5

Bus 1/2 Up

Indicates that the DC bus is at half of the rated voltage.

6

Bus Up

Indicates that the DC bus is at rated voltage.

7

Enable

Indicates that the RGU control is enabled.

8

DSP Ready

Indicates that the DSP processor is ready.

9

Ctrl Ready

Indicates that the RGU control is ready.

10-14 Not Used

15

Ctrl Running

The RGU control is active.

Bit

8

Bit

9

Bit
10

Bit
11

Bit
12

Bit
13

Bit
14

Bit
15

Bit

0

Bit

1

Bit

2

Bit

3

Bit

4

Bit

5

Bit

6

Bit

7

Bit

8

Bit

9

Bit
10

Bit
11

Bit
12

Bit
13

Bit
14

Bit
15

Bit

0

Bit

1

Bit

2

Bit

3

Bit

4

Bit

5

Bit

6

Bit

7