Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 83

Advertising
background image

Publication 2364F-5.01– October 2003

Installing Your RGU

7-13

3. Push the disconnect lever to on. Turn the start switch to on. The

DC bus and control circuitry will power up.

4. The common DC bus voltage will vary based upon the 3-phase

AC input voltage. Verify that the common DC bus voltage is
within these tolerances (RGU not modulating):

Note: The DC bus voltage should be checked at the DC bus
energized board (EA2) as shown in Figure 7.8.
Please refer to the
appropriate layout drawings earlier in this manual for board
location.

Figure 7.8
Where to Check the DC Bus Voltage

5. Verify that the voltage across X1 to X2 on the secondary side of

control transformer PT1, if supplied, is within this tolerance:

6. Verify that all fans are operational.

7. Verify that the DC Bus Energized pilot light is illuminated.

8. Verify that the Not Faulted pilot light, if supplied, is illuminated.

If it is not illuminated, verify that the contacts of the fault circuit
are closed.

Nominal AC Input

Voltage (V AC)

Nominal DC Bus

Voltage (V DC)

Minimum DC Bus

Voltage (V DC)

Maximum DC Bus

Voltage (V DC)

380

564

483

591

460

683

585

715

575

848

732

894

Nominal AC Control

Voltage (V AC)

Minimum AC Control

Voltage (V AC)

Maximum AC Control

Voltage (V AC)

115

104

126