Chapter 12, Setting up trending, Chapter – Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual
Page 119

Publication 2364F-5.01– October 2003
Chapter
12
Setting Up Trending
Trending is a diagnostic tool that you can use to capture and retain an
input parameter data value until a trigger condition occurs. The RGU
has the capacity to setup and monitor up to 4 parameters, Trend 1
through Trend 4. With trending, you program the:
•
parameter to sample
•
trigger condition
•
sampling rate
•
quantity of samples to be taken after the trigger occurs
•
whether trending is to occur one time or continuously
Parameters used by trending are shown in the table below.
Table 12.1 Trending Parameters
Description
Trend 1 Parameter
Number
Trend 2 Parameter
Number
Trend 3 Parameter
Number
Trend 4 Parameter
Number
source
293
305
317
329
variable X source
294
306
318
330
variable X constant value
295
307
319
331
variable Y source
296
308
320
332
variable Y constant value
297
309
321
333
operator (comparison type)
298
310
322
334
sampling rate
299
311
323
335
quantity of post-trigger samples
300
312
324
336
mode (one-shot or continuous operation)
301
313
325
337
select
302
314
326
338
status
303
315
327
339
output
304
316
328
340