Publication 2364F-5.01– October 2003

Chapter

12

Setting Up Trending

Trending is a diagnostic tool that you can use to capture and retain an
input parameter data value until a trigger condition occurs. The RGU
has the capacity to setup and monitor up to 4 parameters, Trend 1
through Trend 4. With trending, you program the:

parameter to sample

trigger condition

sampling rate

quantity of samples to be taken after the trigger occurs

whether trending is to occur one time or continuously

Parameters used by trending are shown in the table below.

Table 12.1 Trending Parameters

Description

Trend 1 Parameter

Number

Trend 2 Parameter

Number

Trend 3 Parameter

Number

Trend 4 Parameter

Number

source

293

305

317

329

variable X source

294

306

318

330

variable X constant value

295

307

319

331

variable Y source

296

308

320

332

variable Y constant value

297

309

321

333

operator (comparison type)

298

310

322

334

sampling rate

299

311

323

335

quantity of post-trigger samples

300

312

324

336

mode (one-shot or continuous operation)

301

313

325

337

select

302

314

326

338

status

303

315

327

339

output

304

316

328

340