Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 180

Advertising
background image

Publication 2364F-5.01– October 2003

D-36

Programming Parameters

177

Host Fault Status Word 2
[Fault Status 2]

This parameter indicates a number of host fault
conditions.

1 - Fault

0 - No Fault

Parameter Type

Source (Read Only)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

Related Parameters

P178, P179

P178 and P179 determine what conditions are
reported and how the conditions are to be
handled (warning/fault).

Bit

Description

0

Desaturizatn

Indicates a desaturization fault.

1

Board Intlk

Indicates a board interlock condition.

2

HW Bus OverV Indicates that the bus is operating at overvoltage (hardware).

3

HW Line I

Indicates a fault in the line current (hardware).

4

Zero Seq Err

Indicates an zero sequnce error.

5

Phase Lock L

Indicates an error in the phase lock loop.

6

Phase Loss

Indicates a phase has been lost from the AC line.

7

Not Used

8

Not Used

9

Not Used

10

SW Line I

Indicates a fault in the line current (software).

11

I Offset Err

Indicates a current offset fault.

12

DualPort TO

Indicates an error in the dual port time out.

13

Not Used

14

Not Used

15

DSP Fault

Indicates a fault in the DSP.

178

Fault Status 2 Report Mask
[Flt Report Mask 2]

This parameter selects the faults that can be
reported to P177.

1 - Report

0 - Suppress

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

1111 1111 1111 1111

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

Related Parameters

P177, P179

Bit

Description

Bit

Description

0*

Desaturizatn

Reports desaturization errors.

8

Not Used

1*

Board Intlk

Reports board interlock errors.

9

Not Used

2*

HW Bus OverV Reports bus overvoltage conditions (hardware).

10*

SW Line I

Reports line current conditions (software)

3*

HW Line I

Reports line current conditions (hardware).

11*

I Offset Err

Reports current offset errors.

4*

Zero Seq Err

Reports zero sequence errors.

12*

DualPort TO

Reports errors in the dual port time out.

5*

Phase Lock L

Reports phase lock loop.

13

Not Used

6*

Phase Loss

Reports phase losses in the AC line.

14

Not Used

7

Not Used

15*

DSP Fault

Reports DSP faults.

* These items cannot be changed to zero.

Bit

8

Bit

9

Bit
10

Bit
11

Bit
12

Bit
13

Bit
14

Bit
15

Bit

0

Bit

1

Bit

2

Bit

3

Bit

4

Bit

5

Bit

6

Bit

7

Bit

8

Bit

9

Bit
10

Bit
11

Bit
12

Bit
13

Bit
14

Bit
15

Bit

0

Bit

1

Bit

2

Bit

3

Bit

4

Bit

5

Bit

6

Bit

7

Advertising