Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 110

Advertising
background image

Publication 2364F-5.01– October 2003

10-4

Interpreting and Setting Status, Command, and Fault Words

Table 10.2 Descriptions of Bits

Host Processor Command Word (P32)

Bit

Description

0

Clear faults

1

Enable the RGU

2

Reset watt-hour meter

3

Save parameters

4

Recall parameters

5

Initialize parameters using defaults

6

Clear warnings

7

Reset RGU

8

Clear Fault Que

9

Clear Warning Que

10

Disable RGU

11

Reset the RGU

12

RESERVED

13

RESERVED

14

RESERVED

15

RESERVED

Host Processor Status Word 1 (P33)

Bit

Description

0

Hard fault has occurred

1

Warning fault has occurred

2

Clear fault(s) request pending

3

Clear warning(s) request pending

4

Bus control relay closed

5

Bus is at half of its rated voltage

6

Bus is at rated voltage

7

RGU enabled

8

DSP processor is ready

9

Bus control is ready

10

RESERVED

11

RESERVED

12

RESERVED

13

DC bus precharge complete

14

RGU control is ready

15

DC bus is under RGU control

Host Processor Mode Word (P35)

Bit

Description

0

Operate in regenerative mode only

1

Error limitor is enabled

2

Auxiliary limit is used for current limit

3

Linearizer enabled

4

RESERVED

5

RESERVED

6

RESERVED

7

RESERVED

8

RESERVED

9

RESERVED

10

RESERVED

11

RESERVED

12

RESERVED

13

RESERVED

14

RESERVED

15

RESERVED

Host Processor Status Word 2 (P34)

Bit

Description

0

Hard fault has occurred

1

Warning fault has occurred

2

Power factor is lagging

3

I

q

is negative limited

4

Iq is negative limited

5

External clear fault required

6

Regenerating current

7

External enable activated

8

M1 feedback (1=closed)

9

DC bus at voltage

10

Wire overtemperature (I

2

t) monitoring is active

11

Wire overtemperature (I

2

t) warning

12

RESERVED

13

RESERVED

14

RESERVED

15

DC bus is under RGU control