Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 198

Advertising
background image

Publication 2364F-5.01– October 2003

D-54

Programming Parameters

293

Trend 1 Input Indirect
[Trend In Ind]

This parameter designates the parameter to be
output when Trend 1 is triggered.

The source parameter defined here is passed to
the output (P304) when the trending operation is
evaluated as true.

Parameter Type

Sink (Read/Write)

Display Units

Parameter Number

Drive Units

Display Units * 1

Factory Default

0 (no selection)

Minimum Value

0

Maximum Value

Maximum Defined Parameter Number

Related Parameters

P294 to P304 (See P298)

294

Trend 1 Operand Indirect X
[Trend X Ind]

This parameter designates a source parameter to
be analyzed in the Trend 1 evaluation. The
source value is masked with the trend Y value
(P296 or P297). P295 (Trend 1 X Value) is used
as the trend X operand when this parameter is
zero (default).

Parameter Type

Sink (Read/Write)

Display Units

Parameter Number

Drive Units

Display Units * 1

Factory Default

0 (disabled, P295 enabled)

Minimum Value

0

Maximum Value

Maximum Defined Parameter Number

Related Parameters

P293 to P304 (See P298)

295

Trend 1 X Value
[Trend X Value]

This parameter defines a constant to be masked
with the trend Y value (P296 or P297).

To use this parameter, the trend X indirect (P294)
must equal zero.

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0

Minimum Value

-32768

Maximum Value

32767

Related Parameters

P293 to P304 (See P298)

296

Trend 1 Operand Indirect Y
[Trend Y Ind]

This parameter designates a source parameter to
be analyzed in the Trend 1 evaluation. The
source value masks the trend X value (P294 or
P295).

P297 (Trend 1 Y Value) is used instead when this
parameter equals zero (default).

Parameter Type

Sink (Read/Write)

Display Units

Parameter Number

Drive Units

Display Units * 1

Factory Default

0 (disabled, P297 enabled)

Minimum Value

0

Maximum Value

Maximum Defined Parameter Number

Related Parameters

P293 to P304 (See P298)

297

Trend 1 Y Value
[Trend Y Value]

This parameter defines a constant to mask the
trend X value (P294 or P295).

To use this parameter, the trend Y indirect (P296)
must equal zero.

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0

Minimum Value

-32768

Maximum Value

32767

Related Parameters

P293 to P304 (See P298)