Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 202

Advertising
background image

Publication 2364F-5.01– October 2003

D-58

Programming Parameters

310

Trend 2 Operator
[Trend Operator]

This parameter selects the operation to be
performed between trend X (P306 or P307) and
trend Y (P308 or P309). If trending is enabled
(P314), a true result of the operation will cause
the Trend 2 Input parameter value (from P305) to
be passed to the prescribed output (P316).

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0 (GT)

Minimum Value

0

Maximum Value

7

Related Parameters

P305 to P316 (See also P298)

P298 (Trend 1 Operator) shows a sample
diagram of the trending configuration

Value Description

Value Description

0

GTSelects the operation [Trend X must be greater than Trend Y].

4

ANDSelects the operation [Trend X AND Trend Y].

1

LTSelects the operation [Trend X must be less than Trend Y].

5

NANDSelects the operation [Trend X NAND Trend Y].

2

EQSelects the operation [Trend X must be equal to Trend Y].

6

ORSelects the operation [Trend X OR Trend Y].

3

NESelects the operation [Trend X must not be equal to Trend Y].

7

NORSelects the operation [Trend X NOR Trend Y].

311

Trend 2 Sample Rate
[Trend Samp Rate]

This parameter determines the rate of sampling
for the Trend 2 Indirects (P306, P308).

The value of this parameter can be changed in
increments of 0.002 sec.

Parameter Type

Sink (Read/Write)

Display Units

sec

Drive Units

Display Units * 2000

Factory Default

0.000

Minimum Value

0.000

Maximum Value

30.000

Related Parameters

P305 to P316 (See also P298)

312

Trend 2 Post Samples
[Trend Post Samp]

This parameter defines the number of samples
(out of 500) to be allocated for post-trigger
sampling.

Pre-samples + Post samples = 500 (0 to 499)

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

10

Minimum Value

0

Maximum Value

499

Related Parameters

P305 to P316 (See also P298)

313

Trend 2 Mode
[Trend Mode]

This parameter determines the duration of the
trending process. The trending process can be
configured to stop trending after a trigger event
occurs (default), or can continue trending.

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0

Minimum Value

0

Maximum Value

1

Related Parameters

P305 to P316 (See also P298)

Value Description

0

One ShotCommands the trending process to stop after a single trigger event.

1

ContinuousCommands the trending process to run continuously.

314

Trend 2 Select
[Trend Select]

This parameter commands the RGU to enable,
disable, or force trigger Trend 2.

After the RGU processes the command, the value
resets to 3 (No Command).

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

3 (No Command)

Minimum Value

0

Maximum Value

3

Related Parameters

P305 to P316 (See also P298)

Value Description

0

DisableCommands the RGU to disable Trend 2.

1

EnableCommands the RGU to enable Trend 2.

2

Force TrigCommands the RGU to force trigger Trend 2. The trending value (prescribed by P305) will be sent to Trend 2 Output Indirect (P316).

3

No CommandIndicates that no command is issued at this time.

Advertising