Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 200

Advertising
background image

Publication 2364F-5.01– October 2003

D-56

Programming Parameters

301

Trend 1 Mode
[Trend Mode]

This parameter determines the duration of the
trending process. The trending process can be
configured to stop trending after a trigger event
occurs (default), or can continue trending.

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0

Minimum Value

0

Maximum Value

1

Related Parameters

P293 to P304 (See P298)

Value Description

0

One ShotCommands the trending process to stop after a single trigger event.

1

ContinuousCommands the trending process to run continuously.

302

Trend 1 Select
[Trend Select]

This parameter commands the RGU to enable,
disable, or force trigger Trend 1.

After the RGU processes the command, the value
resets to 3 (No Command).

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

3 (No Command)

Minimum Value

0

Maximum Value

3

Related Parameters

P293 to P304 (See P298)

Value Description

0

DisableCommands the RGU to disable Trend 1.

1

EnableCommands the RGU to enable Trend 1.

2

Force TrigCommands the RGU to force trigger Trend 1. The trending value (prescribed by P293) will be sent to Trend 1 Output Indirect (P304).

3

No CommandIndicates that no command is issued at this time.

303

Trend 1 Status
[Trend Status]

This parameter displays the status of Trend 1.

Parameter Type

Sink (Read Only)

Display Units

None

Drive Units

Display Units * 1

Factory Default

1 (Unprogrammed)

Minimum Value

0

Maximum Value

4

Related Parameters

P293 to P304 (See P298)

Value Description

0

UnprogrammedTrend 1 is not programmed.

1

StoppedThe trending operation is stopped (trend X and trend Y values are not being evaluated).

2

RunningThe trending operation is running (trend X and trend Y values are being evaluated).

3

TriggeredThe trending operation between trend X and trend Y is true. The trending value (determined by P293) will be output through P304.

4

Forced TrigTrend 1 is triggered due to a ‘Force Trig’ command from the Trend 1 Select (P302 = 0). The trending value is output.

304

Trend 1 Output Indirect
[Trend Out Ind]

This parameter prescribes the destination of the
trend parameter value (listed in P293). The
trending operation (X [operator] Y) must be
evaluated as true for P304 to output the value
from the trend source.

Parameter Type

Sink (Read/Write)

Display Units

Parameter Number

Drive Units

Display Units * 1

Factory Default

0 (no selection)

Minimum Value

0

Maximum Value

Maximum Defined Parameter Number

Related Parameters

P293 to P303 (See P298)

305

Trend 2 Input Indirect
[Trend In Ind]

This parameter designates the parameter to be
output when Trend 2 is triggered (when the trend
X/trend Y evaluation is true).

The source parameter defined here is passed to

Parameter Type

Sink (Read/Write)

Display Units

Parameter Number

Drive Units

Display Units * 1

Factory Default

0 (no selection)

Minimum Value

0

Maximum Value

Maximum Defined Parameter Number

Related Parameters

P306 to P316 (See also P298)

the output (P316) when the trending operation is
evaluated as true.