Chapter

10

Interpreting and Setting Status, Command,
and Fault Words

Fault Status Indication

The RGU has 4 fault status words. Each fault status word has its own
fault-report-mask word and fault/warning-mask word. The following
table contains a fault status-to-parameter number cross reference:

Use the following table to interpret bit settings in fault status and
mask word:

The items that correspond to each bit in a fault status word/mask are
identified in Table 10.1.

Description

Fault Status Parameter
Number

Fault-Report-Mask
Parameter Number

Fault/Warning-Mask
Parameter Number

Fault Status Word 1

174

175

176

Fault Status Word 2

177

178

179

Fault Status Word 3

180

181

182

Fault Status Word 4

183

184

185

Parameter Type

A Bit Set to "0" Means:

A Bit Set to "1" Means:

Fault Status Word

Not faulted.

A fault/warning has occurred.

Fault-Report-Mask

-

Fault/warning will not be recorded in fault queue or
warning queue.

-

RGU operation will NOT respond to fault or warning.

-

Fault/warning will be recorded in fault queue or warning
queue.

-

If a fault occurs, the hard-fault bit 0 will be set to 1 in
both host status words (Parameters #33 and #34).

-

If a warning occurs, the warning-fault bit 1 will be set to
1 in both host status words (Parameters #33 and #34).

Fault/Warning-Mask

Item set to cause a warning when corresponding fault-
report bit is set to 1.

Item set to cause a fault when corresponding fault-report
bit is set to 1.