Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 149

Advertising
background image

Publication 2364F-5.01– October 2003

Programming Parameters

D-5

11

Rated AC Line Current
[Rated AC Current]

This parameter stores the rated input line current
of the RGU.

Parameter Type

Source (Read/Write)

Display Units

Amp

Drive Units

Display Units * 10

Factory Default

See below

Minimum Value

See below

Maximum Value

See below

Related Parameters

P4, P96, P100, P106

J-code RGUs

K-code RGUs

L-code RGUs

M-code RGUs

N-Code RGUs

Factory Default

76.9

Factory Default

181.8

Factory Default

330.0 (286.0*) Factory Default

678.0 (602.0*) Factory Default 906.0 (802.0*)

Minimum Value

43.4

Minimum Value

93.6

Minimum Value

200.3

Minimum Value

421.4

Minimum Value 561.5

Maximum Value 84.6

Maximum Value 200.0

Maximum Value 363.4

Maximum Value 746.2

Maximum Value 996.6

* Value applies to units with 575V AC inputs

12

AC Line Reactor Inductance
[Line Inductance]

This parameter lists the total inductance of the AC
line reactors (CH1-3) in standalone RGU
configurations. Check the labels on the AC
reactors to verify value.

Parameter Type

Sink (Read Only)

Display Units

uH

Drive Units

Display Units * 1

Factory Default

See below

Minimum Value

0

Maximum Value

3000

Related Parameters

P4

J-code RGUs

K-code RGUs

L-code RGUs

M-code RGUs

N-Code RGUs

Factory
Default

1193 (380/460V)
1853 (575V)

Factory
Default

510 (380/460V)
832 (575V)

Factory
Default

317 (380/460V)
404 (575V)

Factory
Default

137 (380/460V)
191 (575V)

Factory
Default

102 (380/460V)
144 (575V)

13

Utility AC Line Frequency
[Utility AC Freq]

This parameter defines the input frequency of the
RGU. Set to 50 or 60Hz.

Parameter Type

Sink (Read/Write)

Display Units

Hz

Drive Units

Display Units * 1

Factory Default

60

Minimum Value

45

Maximum Value

65

Related Parameters

None

14

Measured AC Line Voltage
[Line Voltage]

This parameter measures the incoming voltage on
the AC line.

Parameter Type

Source (Read Only)

Display Units

Vrms

Drive Units

Display Units * 1

Factory Default

0

Minimum Value

0

Maximum Value

800

Related Parameters

P10, P15

15

AC Line Voltage Calibration
[Line Voltage Cal]

This parameter measures the voltage on the input
line. The RGU must be Disabled (not modulating)
when calibrating with this parameter.

Parameter Type

Sink (Read/Write)

Display Units

%

Drive Units

Display Units * 720/1000

Factory Default

0

Minimum Value

-3.1

Maximum Value

3.1

Related Parameters

P14

To calibrate the measured AC line voltage (P14),
adjust P15 until the value of P14 matches the
reading of the AC input voltage on an external
voltmeter.