Environmental specifications – Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual
Page 136

Publication 2364F-5.01– October 2003
B-4
Specifications
Environmental Specifications
Table B.8 Operating Conditions
Table B.9 Storage Conditions
Figure B.1
Altitude Derate Curve
Figure B.2
Temperature Derate Curve
Altitude
3,300 feet (1,000 meters)
"
Ambient Temperature
0
° to 40° C (32° to 104° F) !
Relative Humidity
5% to 95%, non-condensing
" For altitudes higher than 1000 meters, derate RGU using Figure 2.
! For temperatures greater than 40
° C, derate RGU using Figure 3.
Ambient Temperature
0
° to 40° C (32° to 104° F)
Relative Humidity
5% to 95%, non-condensing
80%
85%
90%
95%
100%
105%
0
1,000
2,000
3,000
4,000
(3,300)
(6,600)
(9,900)
(13,200)
Altitu d e
% Rated RGU
Cu rren t
at 40 °C
(ft)
m
75%
80%
85%
90%
95%
100%
105%
0
5
10
15
20
25
30
35
40
45
50
55
(32)
(41)
(50)
(59)
(68)
(77)
(86)
(95)
(104) (113) (122) (131)
Ambient Temperature
% Rated RGU
Current at
Sea Level
°C
(°F)