Environmental specifications – Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 136

Advertising
background image

Publication 2364F-5.01– October 2003

B-4

Specifications

Environmental Specifications

Table B.8 Operating Conditions

Table B.9 Storage Conditions

Figure B.1
Altitude Derate Curve

Figure B.2
Temperature Derate Curve

Altitude

3,300 feet (1,000 meters)

"

Ambient Temperature

0

° to 40° C (32° to 104° F) !

Relative Humidity

5% to 95%, non-condensing

" For altitudes higher than 1000 meters, derate RGU using Figure 2.
! For temperatures greater than 40

° C, derate RGU using Figure 3.

Ambient Temperature

0

° to 40° C (32° to 104° F)

Relative Humidity

5% to 95%, non-condensing

80%

85%

90%

95%

100%

105%

0

1,000

2,000

3,000

4,000

(3,300)

(6,600)

(9,900)

(13,200)

Altitu d e

% Rated RGU
Cu rren t
at 40 °C

(ft)

m

75%

80%

85%

90%

95%

100%

105%

0

5

10

15

20

25

30

35

40

45

50

55

(32)

(41)

(50)

(59)

(68)

(77)

(86)

(95)

(104) (113) (122) (131)

Ambient Temperature

% Rated RGU
Current at
Sea Level

°C

(°F)