Publication 2364F-5.01– October 2003

D-28

Programming Parameters

127

Bus Reference Change Rate
[Ref Change Rate]

This parameter specifies the maximum increase
or decrease allowed in the Bus Rate Reference
(P126) per 5ms.

The bus rate limiter uses this value to produce the
rate limited Bus Reference (P128).

Parameter Type

Sink (Read/Write)

Display Units

% of P16

Drive Units

Display Units * 4096/100

Factory Default

0.24

Minimum Value

0.00

Maximum Value

280.00

Related Parameters

P126, P128

128

Bus Reference
[Bus Reference]

This parameter indicates the voltage that needs to
be supplied to the DC bus.

The RGU compares the voltage needed by the DC
bus (P128) with the Bus Feedback (P141). The
difference (P128-P141) signifies the Bus

Parameter Type

Sink (Read/Write)

Display Units

% of P16

Drive Units

Display Units * 4096/100

Factory Default

0.49

Minimum Value

0.00

Maximum Value

280.00

Related Parameters

P126, P128

Error (P142). The PI regulator determines the
gain required, and an Iq Reference (P96) directs
the RGU to supply the required voltage.

129

Bus Reference Automatic
[Bus Ref Auto]

This parameter sends the calculated bus voltage
that needs to be supplied to the DC bus.

This value is determined by a function of the
measured AC voltage and the nominal AC and DC
voltages (P10, P14, P16).

Parameter Type

Source (Read/Write)

Display Units

Volt

Drive Units

Display Units * 4096/P16

Factory Default

0.85 x P16

Minimum Value

0.85 x P16

Maximum Value

1.15 x P16

Related Parameters

P123, P128, P130

This parameter is the default input used for the
Bus Reference (P128), which is selected by the
Voltage Mode Selector (P123).

130

Automatic Bus Reference Tracking
[AutoRef Tracking]

This parameter specifies the percentage over (or
under) the calculated nominal DC bus voltage
(P14 x sqrt(2)) to be commanded through the Bus
Reference Automatic (P129).

Parameter Type

Sink (Read/Write)

Display Units

% of (P14 x sqrt(2))

Drive Units

Display Units * 5793/100

Factory Default

4.2

Minimum Value

-5.0

Maximum Value

10.0

Related Parameters

P14, P123, P129

For example, if an RGU is supplied with 460V AC, the
calculated nominal DC bus voltage would be 650V
(460V x sqrt(2)). The bus reference calculator would
multiply this 650V x P130 (4.2% ,default) resulting in
27V DC, which would be added to the calculated
Nominal DC Bus Voltage and be stored in P129
(Automatic Bus Reference), which would command
that the DC bus be supplied with 683V DC.

131-136

P131-P136 are for internal use only.