Adjusting Voltage and Current Regulation Parameters

9-5

Monitoring the DC Bus Feedback

The DC bus feedback is a measurement of the DC bus voltage. Refer
to Figure 9.4 For a firmware diagram that monitors the DC bus
feedback.

Three different feedback references are available. Each reference
provides the same voltage feedback at a different reference point in
the processor. We recommend that you use the default setting (0) for
P139.

The bus feedback is then scaled. When the feedback select (P219) is
set to "0", the bus feedback is applied to the feedback filter. The
feedback filter is configured using P137 and P138. Finally, P141
provides the DC bus feedback.

Figure 9.4
Firmware Diagram for Monitoring the DC Bus Feedback

kn

256 S + wn

S + wn

Feedback

Scaling

138

137

140

143

16

144

139

1/4

1/4

0

1

2

38

60

61

DC Bus
Feedback

X

X

Y

X

X

X

*

Indirect, parameter X

Source; parameter X

Sink; parameter X

Parameter X, bit Y

Battery-backed, parameter X

SYMBOL KEY

141

Parameter Number

Parameter Name

16

Nominal DC Voltage

38

Host A/D Converter Input 2

60

DSP DC Bus Voltage

61

DSP Averaged DC Bus Voltage

137

Wn, Bus Feedback Filter Bandwidth

138

Kn, Bus Feedback Filter Gain

139

Voltage Input Select

140

Prefiltered Feedback

141

DC Bus Feedback

143

Scaled Bus Feedback

144

Bus Feedback Calibration