Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 162

Advertising
background image

Publication 2364F-5.01– October 2003

D-18

Programming Parameters

83

It Foldback Current Limit
[It Fldbk Cur Lim]

This parameter indicates what percentage of the
rated DC bus current is being supplied by the
RGU. The percentage decreases as the heatsink
temperature increases.

Parameter Type

Source (Read Only)

Display Units

%

Drive Units

Display Units * 5120/100

Factory Default

300

Minimum Value

0

Maximum Value

300

A value of 300% is displayed when the RGU is
not enabled.

84

Voltage Regulator Output
[Linear PI Out]

This parameter indicates the current reference
from the PI regulator (P121) after it has passed
the linearizer. Note that P35 bit 3 must be set to 1
to activate the linearizer.

Parameter Type

Source (Read Only)

Display Units

% of P11

Drive Units

Display Units * 5120/100

Factory Default

0

Minimum Value

-640

Maximum Value

640

Related Parameters

P35, P121

The value is displayed as a percentage of the
Rated AC Line Current (P11).