Programming Parameters
83
It Foldback Current Limit
[It Fldbk Cur Lim]
This parameter indicates what percentage of the
rated DC bus current is being supplied by the
RGU. The percentage decreases as the heatsink
temperature increases.
Parameter Type
Source (Read Only)
Display Units
%
Drive Units
Display Units * 5120/100
Factory Default
300
Minimum Value
0
Maximum Value
300
A value of 300% is displayed when the RGU is
not enabled.
84
Voltage Regulator Output
[Linear PI Out]
This parameter indicates the current reference
from the PI regulator (P121) after it has passed
the linearizer. Note that P35 bit 3 must be set to 1
to activate the linearizer.
Parameter Type
Source (Read Only)
Display Units
% of P11
Drive Units
Display Units * 5120/100
Factory Default
0
Minimum Value
-640
Maximum Value
640
Related Parameters
P35, P121
The value is displayed as a percentage of the