Publication 2364F-5.01– October 2003

D-34

Programming Parameters

166-173

P166-P173 are for internal use only.

174

Host Fault Status Word 1
[Fault Status 1]

This parameter indicates a number of host fault
conditions.

1 - Fault

0 - No Fault

Parameter Type

Source (Read Only)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

Related Parameters

P175, P176

P175 and P176 determine what conditions are
reported and how the conditions are to be
handled (warning/fault).

Bit

Description

0

ROM Bad CRC Indicates that a ROM fault has been detected.

1

RAM Error

Indicates a fault in the RAM.

2

BatRAM Err

Indicates a fault in the battery-backed RAM.

3

DSP Load

Indicates a DSP loading fault.

4

FPGA Load

Indicates an FPGA loading fault.

5

Iq Foldback

Indicates an Iq foldback fault.

6

M1 Open

Indicates that the M1 contactor has opened (P9).

7

SCANport Err

Indicates an error in the SCANport.

8

R2R HW Error

Indicates an error in the RGU-to-RGU hardware.

9

Control Volt

Indicates a control voltage fault.

10

H/S Overtemp

Indicates that the heatsink temperature (P87) has exceeded maximum.

11

Bus Low

Indicates that the DC bus voltage has fallen below the DC Bus Low Setting (P28).

12

Bus High

Indicates that the DC bus voltage has risen above the DC Bus High Setting (P29).

13

BRAM Chksum Indicates a parity error in the battery-backed RAM.

14

Prchrg Fail

Indicates that the precharge operation has failed.

15

DSP Timeout

Indicates that the DSP has timed out.